MIURA EX Series
Industrial steam system
Brand: MIURA
MIURA EX gas-fired (NG/LPG) single-pass steam boilers have an output of 500 and 750 kg/h. The manufacturer states efficiency up to 94%; they include safety alarms and simple controls.



Features
- Output: 500–750 kg/h
- Efficiency: up to 94%
- Water-tube temperature is continuously measured; combustion is automatically stopped if the set limit is exceeded.
- A blowdown timer signals the discharge time based on the burn duration and the high-flame equivalent.
- A conductivity sensor tracks the boiler water concentration; water is automatically discharged from below the separator when the limit is exceeded.
- Dual water-level control and a compensation electrode directly track the water in the tube during start-up and low loads; designed to reduce thermal stress and alkaline corrosion.
- A primary separator in the header and a secondary cyclone separator control carryover of water with the steam during sudden load changes.
Specifications
| Boiler type | Single-pass steam boiler |
|---|
| Steam output | 500–750 kg/hour |
|---|
| Max. working pressure | 0.98 MPa |
|---|
| Efficiency | Up to 94% |
|---|
| Power supply | AC 380 V, 50 Hz, 3 phase |
|---|
| Fuel | Natural gas / LPG |
|---|